Fund@RELAY.PROTEON.COM (01/11/90)
>I finally installed our UPS monitoring option and my system >complains "UPS Parameter out of range" when it comes up. >Has anyone got this going successfully? >I have a Everex STEP/20, 8Mb running V2.15 Rev. C SFT with >2 CDC WREN V SCSI drives connected to a Future Domain SCSI controller, >2 Arcnets (at addrs 0x2E0, 0x2F0) and 1 Pronet (0x310) connected >with the SS key card to a American Power Conversion 1200VX. >As the updated manual suggested, I have a file in SYS:SYSTEM >called SERVER.CFG which contains the following lines: >UPS TYPE=3 >UPS IO=230 >UPS DOWN=10 >UPS WAIT=5 >So, what's wrong ? >Pierre Goyette How about putting the UPS WAIT in the allowed range of between 15 and 300 seconds... The jumpbers should be set at S2, S4, S8 and S10. That will do the trick. Glenn Fund Internet: Fund@Relay.proteon.com Principal Research Specialist CompuServe: 75170,1060 Sanders Associates cc:Mail Fund at Proteonwebo DW Highway South Phone: (603) 885-6242 MS NHQ4-0138 Director of The Greater Boston Area Nashua, NH 03061 Novell Users Group. Co-Founder and President of the Affiliation of NetWare Users "ANU Day Is Dawning"