[net.analog] Circuit breakers on power lines

roy@phri.UUCP (Roy Smith) (11/17/85)

	Let me preface this all by urging anyone with a more than passing
interest in power distribution to get a copy of Power System Analysis, by
Charles A. Gross (John Wiley & Sons, 1979).

> Typical reaction at the substation to overload is to shutdown the circuit
> and recycle it back up a few moments later.  This is retried until the
> fault is cleared.

	The little gizmos that do this are called reclosers.  According to
Gross they are used on distribution circuits in the 2.4 to 46 kV range
(which is usually the high side of the pole transformers).  To quote:
"Since most faults are self-clearing, reclosers operate on the principle
that if the circuit is de-energized a short time there is a good chance
that whatever caused the fault was vaporized and the ionized arc path has
dissipated."  By 'whatever', they usually mean small animal, but copper
rods will vaporize and dissipate just as well (assuming your house doesn't
first).

	Typical operation involves opening the circuit when there is a
fault and then reclosing it after 20 cycles (1/3 second).  If the fault is
still there, is opens and tries reclosing after another 15 seconds.  If
this fails, it makes a final attempt to reclose the circuit after another
45 seconds.  If the fault still hasn't been cleared, it locks out and the
guys in the yellow trucks have to go out and fix it manually.

	The problems of fault protection on power distribution lines fills
several chapters in Gross (an introductory book).  Several things make the
subject more complicated than just "big circuit breakers".

	We're talking 3-phase balanced circuits here.  No longer is "short
circuit" a useful description.  Is it a phase-to-phase, phase-to-neutral,
or balanced fault?  It makes a big difference which it is.  Shorting the
two big wires that come into your house will probably be phase-to-neutral.

	The breakers you are used to seeing are self-contained over-current
devices only.  Power line breakers often have a remote sensing relay; the
decision to open the line is made at point X, but the actual circuit
interruption is made at point Y.  The relays are usually programmable; one
might be set to trip in 6 seconds on a 175% overload and in 1 second on a
2000% overload.  Most breakers with current ratings over about 250 A will
probably have some sort of setable time-delay; ask the engineer where you
work for a tour of the power room to see what I'm talking about.

	Relays are often directional; a given relay might trip if the fault
is on one side of it but not on the other.  Relays can also be set up to
detect voltage, impedance, or phase problems as well as current overloads.

	The situation is complex, but suffice it to say that you probably
do not want to replace your house's main cartridge fuses with copper rods.
As a side note, most circuit breakers are backed up with fuses because
breakers are mechanical and may fail when you need them most (especially
under extreme overload when they may lock up before tripping).  There isn't
too much that can go wrong with a fuse.
-- 
Roy Smith <allegra!phri!roy>
System Administrator, Public Health Research Institute
455 First Avenue, New York, NY 10016